GB/T 11129-1989 Determination of Water Separation Index of Jet Fuels

AI-translated method card — human verification pending. This is not an official translation of the standard. Unclear source values remain unverified; check the original standard and product certificate before use.

Card type: Test method

1. Method number / full name / English name / replacement relationship

2. Scope of application and non-applicability

3. Method principle

In a water separation index tester, after water and fuel form an emulsion, it quantitatively passes through a coalescer cell equipped with a standard filter pad, and the turbidity of the fuel after passing through the coalescer is measured by a photocell.

4. Reagents and materials (purity / preparation)

5. Instruments and equipment

6. Recommended operating conditions

7. Sampling and sample preparation

8. Analytical procedure

Table of water separation index requirements for reference liquids

Dispersant concentration mL/L Standard water separation index Allowable range minimum Allowable range maximum
0 99 97 100
0.2 89 82 94
0.4 80 69 88
0.6 72 59 83
0.8 65 51 77

Note: For new instruments and when major parts of the instrument are replaced or abnormalities are found, verification must be carried out with the reference liquid, and only when the results meet the requirements in the above table may fuel determination be carried out.

  1. Based on the determination results of 8 laboratories, with a confidence level of 95%.

9. Qualitative and quantitative determination and calculation formulas

10. Precision

11. Report

Take the arithmetic mean of two results that meet the repeatability requirement as the test result.

12. Reference documents

13. Source and verification

This page is an AI translation of the available Chinese method card. Human verification is pending. It is not an official translation of the standard. Check the source standard and product certificate before use.

14. Quick reference for questions and answers

Question Key points of answer
What is the standard number? GB 11129-89.
Chinese name of the standard? Determination of Water Separation Index of Jet Fuel.
English name? Jet fuels - Determination of water separation characteristics.
What standard does it replace? Replaces SY 2233-80.
What standard is referenced and adopted? ASTM D2550-85.
Scope of application? Evaluates the cleanliness of jet fuel, reflects whether surface-active substances such as sulfonates and naphthenates are present, and estimates the ability to separate water when passing through a filter coalescer.
Principle of the method? After water and fuel form an emulsion, it passes quantitatively through a coalescer cell equipped with a standard filter pad, and a photocell measures the turbidity of the fuel after passing through the coalescer.
Definition of water separation index? A numerical value used to evaluate the ease or difficulty of separating water when jet fuel passes through a coalescing medium, in units of 0~100; clean and transparent jet fuel is 100.
What instrument is used? 1104 model CRC water separation index tester.
Requirements for coalescer filter pads? Each test requires a new set of standard filter pads (coarse and fine).
What is the compression gap? 1.588±0.013 mm (0.0625±0.0005 in).
What is the dispersant? Per milliliter of toluene contains 1 mg anhydrous sodium di(2-ethylhexyl) sulfosuccinate (penetrant T).
Water separation index range of reference base fuel? 98~100.
Dispersant concentration range of reference liquid? 0~0.8 mL/L.
Instrument warm-up time? Stabilize for 15 min.
Fuel temperature during emulsification? 24–27 °C (75–80 °F).
Emulsification pressure? 552±14 kPa (80±2 psig).
Volume and time of water injection? 2 mL distilled water, injected uniformly within 60±15 s.
Emulsification circulation time? 5 min.
Test run flow rate? 150 mL/min.
Reading recording time? Record once every two minutes, until the eighth minute.
Which value is taken as the result? The photoelectric meter indicated value at the eighth minute.
Report result? Take the arithmetic mean of two results that meet the repeatability requirement.
How is precision specified? Repeatability and reproducibility according to the curves in Figure 4, with 95% confidence level; specific values not provided in the available source.
Can samples be pre-filtered? They must not be pre-filtered; if contaminated by solid particles, separation by sedimentation is allowed.
Recommended sample containers? Epoxy resin-lined containers are best; carbon steel drums, stainless steel drums, hard glass bottles, and polytetrafluoroethylene containers may also be used; polyethylene and polypropylene plastic drums must not be used.
Pump output requirement? At 689 kPa (100 psig), 415±15 mL/min; if lower than 400 mL/min, the pump should be replaced.
Flow calibration standard? 40 s flows out 100 mL fuel.
Acceptance requirement for reference liquid test? Meets the allowable range in the 6.1.5 reference liquid water separation index requirements table.
What appendices are there? A detailed instrument description, B maintenance and troubleshooting, C preparation of reference base fuel, D preparation and testing of reference liquid, E sample containers and sampling techniques.