NB/SH/T 0699-2023 Test method for compatibility between refrigeration oils and refrigerants

AI-translated method card — human verification pending. This is not an official translation of the standard. Unclear source values remain unverified; check the original standard and product certificate before use.

Card type: Test method

1. Method number / full name / English name / replacement relationship

2. Scope of application and non-applicability

3. Method principle

Place a specified amount of sample and refrigerant into a test tube, raise the temperature at room temperature or in a water bath so that the test oil and refrigerant become a uniform, transparent solution, then cool the test tube in a cooling bath, and measure the temperature at which the solution separates into two phases or the solution as a whole becomes turbid, as the two-phase separation temperature value, to evaluate the compatibility of the refrigeration oil and refrigerant (Chapter 4).

4. Reagents and materials (purity / preparation)

5. Instruments and equipment

6. Recommended operating conditions

7. Sampling and sample preparation

8. Analytical procedure

9. Qualitative and quantitative determination and calculation formulas

10. Precision

11. Report

12. Referenced documents

13. Source and verification

This page is an AI translation of the available Chinese method card. Human verification is pending. It is not an official translation of the standard. Check the source standard and product certificate before use.

14. Quick reference for questions and answers

Question Key points of answer
What is the method number and name of this standard? NB/SH/T 0699—2023 Test method for miscibility of refrigeration oil and refrigerant.
Which version does it replace? Replaces SH/T 0699—2000.
Date of publication and implementation? Published on 2023-02-06, implemented on 2023-08-06.
Scope of application? Specifies the test method for miscibility of refrigeration oil and refrigerant; applicable to refrigeration oil.
Method principle? A specified amount of sample and refrigerant are placed in a test tube, heated to form a uniform transparent solution, then cooled, and the temperature at which separation into two phases or overall turbidity occurs is measured as the two-phase separation temperature.
Representative refrigerant? HFC-134a (1,1,1,2- tetrafluoroethane).
Test tube capacity and pressure resistance? 100 mL pressure-resistant glass test tube, should be able to withstand pressure below 1.96 MPa.
Working pressure of test tube method safety valve? 1.47 MPa.
Actuation pressure of test cell safety valve? Automatically opens when pressure exceeds 4.5 MPa.
Weighed amount of test oil? 7.50 g±0.10 g.
Weighed amount of refrigerant? 42.50 g±0.50 g.
Maximum measurement temperature of test tube method? HCFC-22: 38℃; HFC-134a: 54℃; HFC-32: 19℃.
Maximum measurement temperature of test cell method? HCFC-22: 90℃; HFC-134a: 100℃; HFC-32: 66℃.
Cooling/heating rate? 1℃/min.
Temperature difference between cooling bath and solution in test tube? Maintained within 5℃.
Temperature difference between high-temperature bath and solution in test cell? Not exceeding 5℃.
Repeatability r? Same laboratory, same operator, same instrument, the difference between two test results shall not exceed 2℃.
Reproducibility R? Different laboratories, different operators, different instruments, the difference between two test results shall not exceed 5℃.
Does reproducibility apply to high-temperature and high-pressure miscibility testing? Not applicable (Note: Reproducibility does not apply to 10.2).
To what accuracy is the result report temperature? 1℃.
What does oil content 15% (mass) correspond to? 11.1 specifies that the temperature measured in 10.1 and 10.2 is the two-phase separation temperature at an oil content of 15% (mass).
What are the referenced documents? GB/T 6682—2008, GB/T 7373, GB/T 18826, HG/T 4634.
Vacuum pump evacuation requirement? Can be evacuated to a vacuum degree of 13.3 Pa.
Balance sensitivity? 0.01 g.
Maximum pressure of pressure-resistant hose? 7.84 MPa.
Pressure resistance of the middle main body of the test chamber? Not lower than 6.0 MPa.
Upper pressure limit of the test chamber? Must not exceed 6.0 MPa.
Upper pressure limit of the test tube? Must not exceed 1.96 MPa.

Related public products

Method references do not confirm that a product is suitable for this edition. Check its certificate and availability.

Search related products

Source and review status

This translation has not received a complete independent technical review. Missing sections and unclear source values remain identified above.