NB/SH/T 0811-2023 Determination of oxidation stability of insulating oils

AI-translated method card — human verification pending. This is not an official translation of the standard. Unclear source values remain unverified; check the original standard and product certificate before use.

Card type: Test method

1. Method number / full title / English title / replacement relationship

2. Scope of application and non-applicability

3. Method principle

A solid copper catalyst is placed in the sample to be tested, air is passed in at a constant rate, and after maintaining at a temperature of 120℃ for a certain time, the antioxidant capacity is evaluated by determining the volatile acid value, oil-soluble acid value, sediment content, and dielectric loss factor of the oxidized oil. The test duration may be determined according to the requirements of the corresponding product standards for different types of insulating oils.

4. Reagents and materials (purity / preparation)

4.1 Reagents

4.2 Materials

5. Instruments and equipment

6. Recommended operating conditions

7. Sampling and sample preparation

8. Analysis procedure

8.1 Installation and commissioning (9.1)

8.2 Oxidation (9.2)

Under conditions of maintaining a temperature of 120.0℃±0.5℃ and an air flow rate of 0.150L/h±0.015L/h, oxidize the insulating oil for a certain duration. This duration is determined by the corresponding product standard; typically, for mineral insulating oil without inhibitor 164h, and for mineral insulating oil with inhibitor 500h. Check the air flow rate and temperature daily.

8.3 Determination of sediment (9.2.1~9.2.6)

8.4 Determination of oil-soluble acid (SA) (9.3)

8.5 Determination of volatile acid (VA) (9.4)

8.6 Determination of dielectric dissipation factor (DDF) (9.6)

Remove the oxidation tube from the oxidation bath, store at room temperature 20℃±5℃ for 24h, during which the sample cools naturally and insoluble sediment settles to the bottom. Then transfer the insulating oil to a clean test cup without stirring, ensuring that no sediment enters the test cup. Only about 80% of the insulating oil is transferred to the test cup; the remaining insulating oil and sediment are not used for the dielectric dissipation factor determination. The test method is carried out according to GB/T 5654.

8.7 Determination of oxidation stability of synthetic ester transformer oil (9.7 and Appendix A)

For the oxidation stability of synthetic ester transformer oil, in addition to the above method, the method in Appendix A can also be used.

9. Qualitative and quantitative and calculation formulas

9.1 Oil-soluble acid value (Formula 1)

X_SA = (V₂ − V₁) × M × 56.1 / m

9.2 Volatile acid value (Formula 2)

X_VA = V × M × 56.1 / m

9.3 Total acid value (Formula 3)

X_TA = X_SA + X_VA

9.4 Sediment

Total sediment mass = mass of sediment obtained by acetone dissolution + mass of sediment obtained by n-heptane washing and filtration, expressed as a percentage of the initial mass of the insulating oil.

10. Precision

10.1 Overview

The precision for mineral insulating oil samples without inhibitor was obtained by statistical calculation after 164h test. The precision for mineral insulating oil samples with inhibitor was obtained from an interlaboratory study involving 6 laboratories, which examined 8 samples after oxidation for 500h with total acid value less than 0.1mg/g (calculated as KOH), sediment less than 0.1%, and dielectric dissipation factor (90℃) less than 0.3; determined by statistical analysis of the interlaboratory study results according to GB/T 6683.1. The reliability of test results is judged according to the following provisions (95% confidence level).

10.2 Repeatability (r)

The difference between two consecutive test results obtained by the same operator, in the same laboratory, using the same apparatus, following the same method, on the same sample shall not exceed the values specified in Table 2 and Table 3.

10.3 Reproducibility (R)

The difference between two single, independent test results obtained by different operators, in different laboratories, using different apparatus, following the same method, on the same sample shall not exceed the values specified in Table 2 and Table 3.

Table 2 Repeatability and reproducibility of oxidation stability test for mineral oil without inhibitor under conditions of 120℃, 164h

Oxidized oil parameter Repeatability r Reproducibility R
Total acid value (calculated as KOH)/(mg/g) 16%X₁ 52%X₂
Sediment (mass fraction)/% 24%X₁ 87%X₂
Dielectric dissipation factor (90℃) 17%X₁ 52%X₂

Note: X₁—average of two replicate test results; X₂—average of two single, independent test results.

Table 3 Repeatability and reproducibility of oxidation stability test for mineral oil with inhibitor under conditions of 120℃, 500h

Oxidized oil parameter Repeatability r Reproducibility R
Total acid value (calculated as KOH)/(mg/g) 0.003 0.008
Sediment (mass fraction)/% 0.007 0.010
Dielectric dissipation factor (90℃) 0.002 0.008

Note: The precision applies to mineral oils whose total acid value after oxidation is less than 0.1mg/g (expressed as KOH), sediment less than 0.1%, and dielectric dissipation factor (90℃) less than 0.3.

Table A.1 Precision of oxidation stability test for additive-containing synthetic ester insulating oils

Parameter r R
Oil-soluble acid (expressed as KOH)/(mg/g) 0.12X₁ 0.31X₂
Dielectric dissipation factor (90℃) 0.26X₁ 0.99X₂

Note: X₁—the average of two replicate test results; X₂—the average of two single, independent test results. The precision in Table A.1 was obtained by statistical calculation from ester insulating oil samples after the 164h test.

11. Report

The report shall include the following:

Appendix A The result report shall include:

12. Normative References

Normative References

Bibliography

13. Source and verification

This page is an AI translation of the available Chinese method card. Human verification is pending. It is not an official translation of the standard. Check the source standard and product certificate before use.

14. Quick Q&A

Question Key answer points
Standard number and name? NB/SH/T 0811—2023 Determination of oxidation stability of insulating oils
Which version does it replace? Replaces NB/SH/T 0811—2010 "Determination of oxidation stability of unused hydrocarbon insulating oils"
Adopts an international standard? Modified adoption of IEC 61125:2018 (MOD)
Scope of application? Insulating oils, including unused mineral insulating oils and non-mineral insulating oils, with or without inhibitors
Method principle? Copper catalyst, constant-rate air flow, oxidation at 120℃ for a certain time, measure volatile acid value, oil-soluble acid value, sediment, dielectric dissipation factor
Oxidation temperature? 120.0℃±0.5℃
Air flow rate? 0.150L/h±0.015L/h
Oxidation duration? Determined by the product standard; usually 164h for uninhibited mineral oil, 500h for inhibited mineral oil
Sampling standard? GB/T 4756
Sample amount? 25g±0.1g, placed into three oxidation tubes
Catalyst? Soft electrolytic copper wire, surface area 28.6cm²±0.3cm², diameter 1mm~2mm, wound into a spiral with outer diameter 2cm and length 5cm, must not be reused
Absorption tube liquid? 25mL secondary water
Reference for oil-soluble acid determination? NB/SH/T 0836.2 (color indicator method); for dark colors, NB/SH/T 0836 potentiometric titration method may be used
Reference for dielectric dissipation factor determination? GB/T 5654
Total acid value formula? X_TA = X_SA + X_VA
Volatile acid titration endpoint? The solution just turns pink and does not fade within 15s
Sediment drying temperature? 105℃
Precision Table 2 applies? Uninhibited mineral oil 120℃, 164h
Precision Table 3 applies? Inhibited mineral oil 120℃, 500h, and total acid value <0.1mg/g, sediment <0.1%, DDF(90℃)<0.3
Report total acid value precision? 0.01 mg/g (expressed as KOH)
Report sediment precision? 0.01% (mass fraction)
Report dielectric dissipation factor precision? 0.001
Method for ester insulating oils? See 9.7 and Appendix A (informative), 150℃±2℃, 164h, headspace vial method
Appendix A water content requirement? Shall not be greater than 200mg/kg, determined according to NB/SH/T 0207
Appendix A oil sample amount? 37.5mL poured into 50mL glass headspace vial
Appendix A copper sheet dimensions? Surface area approximately 11cm², length 67mm, width 7.5mm, thickness 0.5mm
Appendix A report items? Oil-soluble acid (SA), 90℃ dielectric dissipation factor; optional appearance, kinematic viscosity

Related public products

Method references do not confirm that a product is suitable for this edition. Check its certificate and availability.

Search related products

Source and review status

This translation has not received a complete independent technical review. Missing sections and unclear source values remain identified above.