SH/T 0803-2007 Determination of polychlorinated biphenyl contaminants in insulating oil — Capillary gas chromatography

AI-translated method card — human verification pending. This is not an official translation of the standard. Unclear source values remain unverified; check the original standard and product certificate before use.

Card type: Test method

1. Method number / full name / English name / replacement relationship

2. Scope of application and non-applicability

3. Method principle

4. Reagents and materials (purity / preparation)

5. Instruments and equipment

6. Recommended operating conditions

Injector type Initial isothermal time Initial temperature Temperature control program Hold time at maximum temperature Cool to
Split 0 min~2 min 130℃ 130℃~290℃ (2.5℃/min) 5 min 130℃
Splitless 1 min 50℃ 50%~130℃ (40℃/min), 130~290℃ (2.5℃/min) 5 min 50℃
On-column 0.5 min 70℃ 70~130℃ (40℃/min), 130~290℃ (2.5℃/min) 5 min 70℃

7. Sampling and test sample preparation

8. Analytical procedure

Peak number Reference peak/homologue group number ERRT
9 30 0.000
33 44 0.225
46 56/60 0.342
57 77/110 0.427
74 138/160/163 0.574
90 180 0.703
105 209 1.000
Peak number Segment number Homologue number ERRT (example) RRF (Appendix C)
12 1 18 0.028 0.275
22 2 31 0.114 0.493
33 3 44 0.225 0.460
49 4 101 0.356 0.587
63 5 118 0.477 0.764
74 6 138 0.574 0.726
90 7 180 0.703 1.137
95 8 170 0.759 0.659
102 9 194 0.877 1.640

9. Qualitative and Quantitative and Calculation Formulas

10. Precision

11. Report

12. Normative references

13. Source and verification

This page is an AI translation of the available Chinese method card. Human verification is pending. It is not an official translation of the standard. Check the source standard and product certificate before use.

14. Quick-reference Q&A

Question Key answer points
Standard number and title? SH/T 0803—2007 Determination of polychlorinated biphenyl contaminants in insulating oil—Capillary gas chromatography
Adoption relationship? Modified adoption of IEC 61619: 1997 (MOD)
Issue/implementation dates? Issued on 2007-08-01, implemented on 2008-01-01
Applicable objects? Determination of total content of PCB in non-halogenated insulating oil, especially suitable for detailed congener analysis; suitable for unused, regenerated, and used insulating oil
Not applicable? No explicit exclusion clause is provided in the available source
Detector? High-temperature electron capture detector (ECD)
Chromatographic column? Cross-linked 5% phenylmethylsilicone stationary phase fused silica capillary column, 50 m or 60 m, internal diameter 0.2 mm~0.35 mm, film thickness 0.1 μm~0.25 μm
Carrier gas? Nitrogen or hydrogen, high purity, purity at least 99.99%
Auxiliary gas? Argon:methane (95%:5%) or nitrogen with purity at least 99.99%
Internal standard substances? C209 (DCB) and C30
Sample dilution factor? 100 times
Sampling standard? GB 7597
Purification columns? 3 mL silica gel column (500 mg, 40 μm) + 3 mL benzenesulfonic acid column (500 mg, 40 μm)
Recovery requirement? Greater than 85%
Detection limit? Detection limit for a single peak 0.1 mg/kg; from a quantitative perspective, only those above 2 mg/kg are evaluated (original text source-text extraction noise, requires confirmation against the source standard (source-text extraction))
Repeatability formula? r = 2 + 0.1x
Reproducibility formula? Original text source-text extraction is missing, requires confirmation against the source standard (source-text extraction)
Reporting unit? mg/kg
Annex A? Informative annex, chromatogram of the mixed solution used for testing
Annex B? Informative annex, congeners, retention times, and relative response factors
Annex C? Informative annex, PCB elution order
Annex D? Informative annex, comparison of clause numbers between this standard and IEC 61619: 1997